Fig.49

Clean the condensate collector

1
2
Fig.50
Cleaning the siphon
1
3
5
6
10.4

Specific maintenance work

7625116 - v.04 - 17012017
10.3.9
1. Remove the sealing cap from the condensate collector.
2. Rinse the condensate collector thoroughly with a water flow that is
as large as possible.
3. Put the sealing cap back on the condensate collector.
4. Disconnect the silicon hose of the air pressure differential switch
from the connection nipple on the condensate collector.
5. Clean the opening of the connection nipple thoroughly (by blowing
air or pushing an object through it).
6. Reconnect the silicon hose.
AD-0000129-02

10.3.10 Cleaning the siphon

1. Push the siphon upwards:
2
2. Carefully pull the siphon downwards.
3. Clean the siphon with water.
4. Fill the siphon with water up to the mark.
5. Push the siphon firmly into the designated opening
the boiler.
6. Carefully pull the siphon downwards.
7. Check whether the siphon is firmly fitted in the boiler.
4
7
AD-0000130-02
Perform the specific maintenance work if this proves to be necessary fol­
lowing the standard inspection and maintenance work. To conduct the
specific maintenance work:
Clean the condensate collector
Warning
During rinsing, avoid penetration of water into the boiler or the
control panel.
The siphon should release with a click.
The siphon should snap shut with a click.
Danger
The siphon must always be filled with water. This prevents flue
gases from entering the room.
10 Maintenance
underneath
61