Installation requirements
•
The fireplace must have ventilation openings near the bottom and near the top of the
fireplace to avoid heat accumulation in the fireplace.
•
The total ventilation air inlet openings must have an area of at least 450 cm
example 2 inlet openings with an area of at least 225 cm
•
The total ventilation air outlet openings must have an area of at least 450 cm
example 2 outlet openings with an area of at least 225 cm
6.3
Requirements on the chimney
•
Make sure that in case of use of an existing (masonry) chimney, it is in good order and
applicable for the appliance. Ask your dealer or chimney sweeper for advice.
•
Install a stainless steel pipe (flexible or rigid) chimney in any new or existing masonry
chimney.
•
Make sure to insulate the stainless steel chimney or use double-walled insulated
stainless steel chimney elements.
•
Make sure the flue system obeys the national and local applicable regulations.
•
Do not connect more than one appliance to the same chimney.
•
The flue system must have a temperature class designation of at least T400.
•
Do not use more than 2 bends of 45°.
•
The chimney outlet must be at least 5 meter above the top of the appliance.
•
The chimney outlet must be at least 40 cm above the top of a sloped roof.
•
The chimney outlet must be at least 1 meter above a flat roof.
•
The chimney outlet must be free from any objects (buildings, trees, etc.) within a
horizontal range of at least 5 meter.
•
Make sure your fire insurance policy covers any damage caused by a chimney fire.