Installation requirements
The fireplace must have ventilation openings near the bottom and near the top of the
fireplace to avoid heat accumulation in the fireplace.
The total ventilation air inlet openings must have an area of at least 450 cm
example 2 inlet openings with an area of at least 225 cm
The total ventilation air outlet openings must have an area of at least 450 cm
example 2 outlet openings with an area of at least 225 cm
6.3

Requirements on the chimney

Make sure that in case of use of an existing (masonry) chimney, it is in good order and
applicable for the appliance. Ask your dealer or chimney sweeper for advice.
Install a stainless steel pipe (flexible or rigid) chimney in any new or existing masonry
chimney.
Make sure to insulate the stainless steel chimney or use double-walled insulated
stainless steel chimney elements.
Make sure the flue system obeys the national and local applicable regulations.
Do not connect more than one appliance to the same chimney.
The flue system must have a temperature class designation of at least T400.
Do not use more than 2 bends of 45°.
The chimney outlet must be at least 5 meter above the top of the appliance.
The chimney outlet must be at least 40 cm above the top of a sloped roof.
The chimney outlet must be at least 1 meter above a flat roof.
The chimney outlet must be free from any objects (buildings, trees, etc.) within a
horizontal range of at least 5 meter.
Make sure your fire insurance policy covers any damage caused by a chimney fire.
28
min. 50cm
min. 20cm
2
. (For
2
each.)
2
. (For
2
each.)
Cuatro-7 75-60