Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 508

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

• Pattern B
1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove
the insulation from the cut end of the cable as shown below.
2. Connect the remote controller cable and connecting cable as shown below. Be sure to insu-
late the connection between the cables.
3. Connect the remote controller cable to the connecting cable, and insert it to the connector.
Set the DIP switch (SW1) to "2WIRE" on the PCB of the indoor unit.
NOTE: Layout of terminal block and PCB is varies depending on the type of indoor unit.
¢ Specifications
Input voltage
Power consumption
Usage temperature range
Usage humidity range
Storage temperature range
Storage humidity range
Dimensions
(H × W × D)
Weight
 Wiring specifications
Use
Remote controller
cable
*: Use shielded cable (locally purchased) in accordance with the regional cable standard.
2-7. Wired remote controller (UTY-RLR)
Insulated
connection
Remote
controller cable
(Non-polar)
Set the DIP switch
(SW1) to "2WIRE"
Connect to earth
Functional grounding
(ground) screw
(If necessary)
Remote controller
cable (Non-polar)
Connector
(adapter)
V
W
°C
%
°C
%
mm
g
Cable size
2
0.33 to 1.25 mm
(22 to 16 AWG)
- (05-62) -
20 mm
Remote
controller cable
(Non-polar)
White
Connecting
cable
Red
Black
Cut and
insulate
Indoor unit
PCB
Connector CNC01
Connecting cable
(onboard)
SW1
Indoor unit
PCB
Max. 0.23
0 to 90 (no condensation)
-20 to 70
0 to 90 (no condensation)
120 × 120 × 17
Wire type
Non polar 2-core
DC 12
0 to 46
170
Remarks
Use sheathed twist pair cable.*
2. Control units