 Example 5 (Prohibited)
Outdoor unit
Capacity ratio
Model name
Outdoor unit
AJ045LCLDH
Indoor unit 1 AUXB004GLEH
Indoor unit 2 AUXB004GLEH
Indoor unit 3 AUXB004GLEH
Indoor unit 4 AUXB004GLEH
Indoor unit 5 AUXB004GLEH
Indoor unit 6 AUXB004GLEH
Indoor unit 7 AUXB004GLEH
Indoor unit 8 AUXB004GLEH
Indoor unit 9 AUXB004GLEH
Indoor unit 10 AUXB004GLEH
Indoor unit 11 AUXB004GLEH
Indoor unit 12 AUXB004GLEH
Indoor unit 13 AUXB007GLEH
Indoor unit 14 AUXB007GLEH
1-1. Refrigerant system
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 6 Indoor unit 7 Indoor unit 8 Indoor unit 9 Indoor unit 10
Indoor unit 11
Indoor unit 13
Indoor unit 12
Cooling
Total
capacity
capacity
(kW)
15.1
15.1
1.1
1.1
1.1
1.1
1.1
1.1
(2) 50%
1.1
(1) 17.6
1.1
1.1
1.1
1.1
1.1
2.2
2.2
- (06-4) -
Indoor unit 4
Indoor unit 5
Indoor unit 14
117%
Connectable
indoor unit
capacity
Min.
Max.
(3) 130%
Prohibited → Because 14 indoor
7.6
19.6
Judge
units are connected