 Example 6 (OK)
Outdoor unit
Capacity ratio
Model name
Outdoor unit
AJ045LCLDH
Indoor unit 1 AUXB004GLEH
Indoor unit 2 AUXB004GLEH
Indoor unit 3 AUXB009GLEH
Indoor unit 4 AUXB009GLEH
Indoor unit 5 AUXB009GLEH
Indoor unit 6 AUXB009GLEH
Indoor unit 7 AUXB009GLEH
 Example 7 (OK)
Outdoor unit
Capacity ratio
Model name
Outdoor unit
AJ045LCLDH
Indoor unit 1 AUXB004GLEH
Indoor unit 2 AUXB004GLEH
Indoor unit 3 AUXB009GLEH
Indoor unit 4 AUXB009GLEH
Indoor unit 5 AUXB009GLEH
Indoor unit 6 AUXB009GLEH
Indoor unit 7 AUXB012GLEH
1-1. Refrigerant system
Indoor unit 1
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Cooling
Total
capacity
capacity
14.0
14.0
1.1
1.1
2.8
2.8
(1) 16.2
2.8
2.8
2.8
Indoor unit 1
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Cooling
Total
capacity
capacity
14.0
14.0
1.1
1.1
2.8
2.8
(1) 17.0
2.8
2.8
3.6
- (06-5) -
Connectable
indoor unit
capacity
Min.
Max.
(kW)
(2) 50%
(3) 130%
7.0
18.2
Connectable
indoor unit
capacity
Min.
Max.
(kW)
(2) 50%
(3) 130%
7.0
18.2
116%
Judge
(2) ≤ (1) ≤ (3)
7.0 < 16.2 < 18.2 → OK
121%
Judge
(2) ≤ (1) ≤ (3)
7.0 < 17.0 < 18.2 → OK
1. System design