Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 585

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

¢ Simple procedure for create XIF and register data to Network
converter for LonWorks
Important
Network converter will not operate if,
• VRF network system address (Outdoor and Indoor units address) allocation information are not
registered to Network converter.
• XIF data information and VRF network system address allocation information must not be the
same.
• Binding and commissioning are not executed. (During binding, read out the Network converter
Neuron ID by pushing BMS service switch [SW2] on the main PCB of Network converter.)
• If the ID number registered to the Network converter is not same as the ID number which is in-
cluded in the XIF of Network converter.
NOTE: For detailed information, refer to the application manual which is included inside packaged
CD-ROM.
The following is the on-line procedure. It is also possible to create XIF and register data off-line.
1.
Connect the PC and this product.
Connection will be done by the connector cable provided as an accessory item of this product.
2.
Install tool for convertor (software) in PC.
Tool for convertor is the accessory item of this product.
3.
Set this product to installation mode.
4.
Setting ID number of this product on PC screen of tool for convertor.
(ID number is required to identify this product from BMS. A maximum number of four Network
converters can be connected to one BMS, and ID number allocation is like 00, 01, and so on.)
5.
Initial setting of indoor unit and outdoor unit address by using the tool for convertor.
6.
Register the initial setting data to this product. Click "Register" dialog.
7.
Set configuration properties.
To set the communication properties of this product, select the following communication proper-
ties and types; otherwise, the default value will be used.
• Select communication items
– Event driven communication or Cyclic communication (Default: Cyclic 3 minutes)
– Communication interval time during turning on all together (Default: 3 minutes)
• Select communication type (to communicate data with BMS)
– Communicate only when changing network variable or communicate all network variable.
(Default: Only when changing network variable)
– Communicate only when changing room temperature value (Default: Room temperature
changed value 1 °C)
8.
Register the configuration properties data to this product. Click the "Register" dialog.
9.
Creating/Modifying XIF, and transfer XIF data by USB memory or floppy disk for binding.
10.
Press "Reset SW7" to reset this product.
11.
Turn off the power. After that, remove the connection of PC and this product respectively.
In this stage, Network converter is ready for binding and commissioning.
3-4. Network converter for LonWorks (UTY-VLGX)