 Indoor unit address setting
NOTE: Perform this setting on the master remote controller.
1.
By pressing the + or - button, select a remote controller address. (Select the indoor unit you
want to operate.) Then pres the ENTER button.
2.
By pressing the + or - button, display function number "01". Then press the ENTER button.
3.
By pressing the + or - button, set up the indoor unit address. (The setting range is from "00" to
"63".)
• When the address data is properly set up on the indoor unit, the set number will be dis-
played. (GOOD)
• When the address data is not set up correctly, "- -" is displayed. (ERROR) Back to the previ-
ous step and set up the indoor unit address data again.
4.
To return to the address selection screen, press the ENTER button. If setting has been com-
pleted, press MENU button to return to the Menu 2 item selection screen.
1-4. Address setting by remote controller
Example: When remote controller address "01" is selected
Example: When indoor unit address data "12" is set up
ERROR
- (07-52) -
Remote controller address