 Example 3 (Prohibited)
Outdoor unit
Capacity ratio
Model name
Outdoor unit
AJ045LCLDH
Indoor unit 1 ARXD024GLEH
Indoor unit 2 ARXD018GLEH
Indoor unit 3 ARXD018GLEH
 Example 4 (OK)
Capacity ratio
Model name
Outdoor unit
AJ045LCLDH
Indoor unit 1 ARXD024GLEH
1-1. Refrigerant system
Indoor unit 1
Connectable
Cooling
Total
capacity
capacity
Min.
(kW)
14.0
14.0
7.1
(2) 50%
5.6
(1) 18.3
7.0
5.6
Outdoor unit
Connectable
Cooling
Total
capacity
capacity
Min.
(kW)
14.0
14.0
(2) 50%
7.1
(1) 7.1
7.0
- (06-3) -
Indoor unit 2
Indoor unit 3
131%
indoor unit
capacity
Max.
(3) 130%
18.2
18.2 < 18.3 → Prohibited
Indoor unit 1
51%
indoor unit
capacity
Max.
(3) 130%
18.2
7.0 < 7.1 < 18.2 → OK
Judge
(3) < (1)
Judge
(2) ≤ (1) ≤ (3)