• Pattern B
1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove
the insulation from the cut end of the cable as shown below.
2. Connect the remote controller cable and connecting cable as shown below. Be sure to insu-
late the connection between the cables.
3. Connect the remote controller cable to the connecting cable, and insert it to the connector.
Set the DIP switch (SW1) to "2WIRE" on the PCB of the indoor unit.
NOTE: Layout of terminal block and PCB is varies depending on the type of indoor unit.
¢ Specifications
Dimensions (H × W × D)
Weight
 Wiring specifications
Use
Remote controller
cable
*: Use shielded cable in accordance with local rules for remote controller cable.
2-12. Simple remote controller (Without operation mode: UTY-RHR)
Insulated
connection
Remote
controller cable
(Non-polar)
Set the DIP switch
(SW1) to "2WIRE"
Connect to earth
Functional grounding
(ground) screw
(If necessary)
Remote controller
cable (Non-polar)
Connector
(adapter)
mm
Cable size
2
0.33 to 1.25 mm
(22 to 16 AWG)
- (05-86) -
20 mm
Remote
controller cable
(Non-polar)
White
Connecting
cable
Red
Black
Cut and
insulate
Indoor unit
PCB
Connector CNC01
Connecting cable
(onboard)
SW1
Indoor unit
PCB
120 × 75 × 19
g
Cable type
Sheathed cable
Shielded cable*
120
Remarks
Non polar 2-core, Twisted pair
2. Control units