Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 693

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

• Selection of pipe size
Pipe no.
a
b
b1
c
d
e1
e2
f1
f2
f3
• Limitation check
Total pipe length
Between outdoor unit and farthest indoor
unit
Between the first separation tube and the
farthest indoor unit
Between outdoor unit and the nearest
indoor unit
Between outdoor unit and the first
separation tube
• Calculation of additional charge refrigerant
– Calculation of additional amount for pipe length (A)
Diameter of liquid pipe (mm)
Ø9.52
Ø6.35
A = (0.058 kg × 30 m) + (0.021 kg × 30 m) = 2.37 (kg)
– Calculation of factory charge amount (B)
Outdoor unit
B = 4.00 kg
– Total refrigerant amount check (C)
C = A + B = 2.37 + 4.00 = 6.37 (kg) < 6.83 (kg) → OK
Check pipe length and height difference between the units by comparing with
page 06-20.
2-6. Piping design example
Liquid pipe
Ø9.52
Ø9.52
Ø6.35
Ø9.52
Ø9.52
Ø6.35
Ø6.35
Ø6.35
Ø6.35
Ø6.35
Pipe
Additional amount for pipe
1
Pipe diameter (mm)
Gas pipe
Ø15.88
Ø15.88
Ø12.70
Ø15.88
Ø15.88
Ø12.70
Ø12.70
Ø12.70
Ø12.70
Ø12.70
Example
Diagram
Total
60
a + b + c + f3
30
b + c + f3
20
a + b1
15
a
10
length (kg/m)
0.058
0.021
Model name
AJ045LCLDH
- (06-33) -
Length example
(m)
10
5
5
10
5
5
5
5
5
5
Limitation
Judge
m
80
OK
or less
50
OK
or less
40
OK
or less
5
OK
or more
3
OK
or more
Liquid pipe length (m)
30
30
Factory charge amount (kg)
4.00
"Piping limitation"
2. Piping design