Power Requirements

The standard iSTAR eX uses the UL Recognized ESD Power Supply, Model SPS-6.5 with
Battery charger.
To ensure adequate power, calculate the total power requirements of iSTAR eX and its related
hardware, as follows.
Add the total current power for components in the system (modules, relays, optional
modules, readers, and wire resistance).
Use the information in Table 1-3 through Table 1-5 to compute the current draw of
components attached to iSTAR eX.
The standard iSTAR eX must be connected to a 15A circuit breaker protected branch circuit.
Cabling must be UL Listed. See the section "Connecting AC Power to UL Recognized ESD
Power Supply" on
page

iSTAR eX Components and Boards

Table 1-3 shows the power requirements of iSTAR eX components and attached boards.
Table 1-3: Component and Board Power Requirements
Component/Board
iSTAR eX - GCM and PMB
iSTAR eX GCM board
iSTAR eX PMB board
a
RM-4 board
b
RM-4E board
I/8 board
R/8 board
a
RM-4 board has only been evaluated by UL with RM Series readers (RM 1,2,3)
b
RM-4E boards have only been evaluated by UL for use with RM-DCM-2 enclosure.

iSTAR eX Input Power Rating

The iSTAR eX has the following input power ratings when using the internal power supply:
100 - 240 VAC
6.2 Amps
1-23.
Current Draw at 12VDC
500 mA with LCD - no load
350 mA with LCD - no load
150 mA - no load
80 mA without LCD - no load
180 mA with LCD - no load
125 mA - no load
125 mA - no load
150 mA - no active relays.
Add 20 mA for each active relay
Installation Requirements
1–15