2.3.2 Wire Routing for Power & Non-Power
Limited
All wiring entry points are designated on the diagram by arrows. All
circuits are classified UL installation power limited except for the
battery leads which are not power limited.
A minimum ¼" (6.4mm) separation must be maintained at all points
between power limited and non-power limited wiring and connec-
tions. See page 115 for expanded diagrams.
Diagram 2-1: Wiring Routing
Stand Of f
PC Boar d
Cabinet
Primary:120V AC/60Hz.
Secondary: 16.5VDC 40V A
DSCPTD 1640U
Class II Tr ansf ormer
NO TE: Do not connect
transformer to receptacle
controlled by a switch
NON-POWER LIMITED
NOTE: Wire entry for power limited wiring must be separated by a dif-
ferent entry access from non-power limited wiring.

2.3.3 Corbus Wiring

The RED and BLK Corbus terminals are used to provide power
while YEL and GRN are used for data communications. The 4 Cor-
bus terminals of the alarm controller must be connected to the 4 Cor-
bus terminals or wires of each module.
The following conditions apply:
Corbus should be run with minimum 22 gauge quad. two pair
twisted preferred.
The modules can be home run to the panel, connected in series
or can be T-tapped.
NOTE: Any module can be connected anywhere along the Corbus. Sep-
arate wire runs for keypads, zone expanders etc. are not necessary.
NOTE: No module can be more than 1,000'/305m (in wire length) from
the panel. Do not use shielded wire for Corbus wiring.
Diagram 2-2: Corbus Wiring
Module (A) is wired correctly as it is
within 1,000'/305m of the panel, in
wire distance. Module (B) is wired
correctly as it is within 1,000'/305m
of the panel, in wire distance. Module
(C) is NOT wired correctly as it is
farther than 1,000'/305m from the
panel.
Current Ratings
In order for the system to operate properly, the power output of the
alarm controller and power supply modules cannot be exceeded. Use
the data below to ensure that the available current is not exceeded.
North America Only
POWER LIMITED
Cable Tie (not supplied) recommended
UA 503
DSC
HS2016/032/064/128
WARNING:
High Voltage . Disconnect AC Power
and telephone lines before servicing
HS2016-4
HS2016-4
HS2064
HS2032
HS2064
HS2128
HS2128
Only
CON1
Only
TB-2
BAT+BA T-
AC
+ AUX - + BELL
-
RED
BLK
YEL GRN
1
PGM
2
3
PGM
4
Z1 COM Z2
Z3
COM
Z4
Z5
COM
Z6
Z7
COM
Z8 GND
Ring
Tip
R-1 T-1
PE (Protective Earth)
12V / 7 AHr
12V / 7 AHr
BLACK
RED
DSC Model BD7-12
or equivalent
Battery
StandbyTime:
24Hrs min.
firealarmresources.com
S e c t i o n
Table 2-1: System Output Ratings
Device
Output
HS2016
AUX:
700mA. Subtract the listed rating for each
HS2032
keypad, expansion module and accessory
HS2064
connected to AUX or Corbus. At least
HS2128
100mA must be reserved for the Corbus.
BELL:
700mA. continuous rating.
2.0A. short term. Available only with
standby battery connected. Not for UL/
ULC or EN certified applications
HSM2208
AUX:
250mA.Continuous rating. Subtract for
each device connected. Subtract the total
load on this terminal from the alarm panel
AUX/Corbus output.
HSM2108 AUX:
100mA. Subtract for each device
connected. Subtract the total load on this
terminal from the panel AUX/Corbus
output.
Alarm Controller Current Calculation
Maximum (Standby or Alarm)
AUX (700mA max. including
PGMs 1-4)
Corbus (700mA max.)***
PCLink+ (Alt. Com.:125mA)
Total (must not exceed 700mA)
***See Corbus Current Calculation Chart.
For UL, ULC and Commercial Listed applications, the total standby and
alarm current cannot exceed 700mA.
Table 2-2:Corbus Current Calculation Chart
Item
Current (mA)
HS2LCD
100
HS2ICN
100
HS2LED
100
HS2LCDP
100
HS2ICNP
100
HS2LCDRF
100
HS2ICNRF
100
HS2ICNRFP
100
Current required for connected devices =
HSM2108*
30
HSM2208*
40
HSM2300/2204*
35
HSM2HOSTx
35
3G2080(R)/
125 (PCLINK) x
TL2803G(R)/
TL280(R)
Total Corbus Current =
*These units draw current from the Corbus to power devices external
to the module. This current must be added to the total Corbus current.
See manufacturer's specifications for the current draw of each device.
4
2 :
I n s t a l l a t i o n
Rating (12V
DC)
x Quantity
Total (mA)
x
x
x
x
x
x
x
x
x
x
x
x