Connecting Ac Power To Ul Recognized Esd Power Supply; Grounding Procedure - Tyco Software House iSTAR eX Installation Manual

Table of Contents

Advertisement

Connecting AC Power to UL Recognized ESD Power Supply

ESD Power Supply
B

Grounding Procedure

iSTAR eX must be connected to a 15A circuit breaker protected branch circuit connected
through conduit with minimum 18 AWG wire. Cabling must be UL Listed.
Disconnect Power before servicing the unit.
iSTAR eX line voltage connections must comply with NEC requirements.
Figure 1-11 shows a photo of the UL Recognized ESD power supply, Model SPS-6.5, and line
voltage connections to an iSTAR eX.
A
To ground the iSTAR eX, refer to Figure 1-11 and perform these steps:
1. Connect the incoming ground wire (green or green/yellow) to the ground lug as shown in
point A.
2. Connect the ground input of the ESD power supply to the ground lug as shown in point A.
3. Be sure the door is also grounded as shown in point B.
Connecting AC Power to UL Recognized ESD Power Supply
Figure 1-11: Standard AC Power and Grounding
1–23