Exhaust Requirements

Risk of fire. A clothes dryer produces combustible
lint. Exhaust outdoors. Consult technical instruc-
tions for detailed exhaust specifications.
To reduce the risk of fire, DO NOT use plastic or thin
foil ducting to exhaust the tumble dryer.
To reduce the risk of fire and accumulation of com-
bustible gases, DO NOT exhaust tumble dryer air in-
to a window well, gas vent, chimney or enclosed, un-
ventilated area such as an attic wall, ceiling, crawl
space under a building, or concealed space of a
building.

Layout

Whenever possible, install tumble dryers along an outside wall
where duct length can be kept to a minimum, and make-up air
can be easily accessed. Construction must not block the airflow at
the rear of the tumble dryer. Doing so would prevent adequate air
supply to the tumble dryer combustion chamber.
©
Published by permission of the copyright owner -
DO NOT COPY or TRANSMIT
Exhaust Requirements
CAUTION
WARNING
WARNING

Make-Up Air

A tumble dryer is forced air exhausted and requires provisions for
make-up air to replace air exhausted by tumble dryer.
IMPORTANT: Do not obstruct flow of combustion and
ventilation air.
Required Make-Up Air Opening (to the outside) for
Each Tumble Dryer, in.
W933
Model
Standard 030 Series
Standard 035/055 Series
W773R1
Eco 035 Series
Standard T30 Series
Eco T30 Series
T45 Series
Make-up air openings with louvers will restrict airflow. The
opening must be increased to compensate for area taken up and
restrictions created by louvers. Contact the louver manufacturer
for the exact specifications.
W059R1
Make-up air openings in rooms containing tumble dryer(s) and/or
gas fired hot water heater or other gravity vented appliances must
be increased sufficiently to prevent downdrafts in any of the
vents when all tumble dryers are in operation. Do not locate grav-
ity vented appliances between tumble dryer(s) and make-up air
openings. If it is necessary to duct make-up air to tumble dry-
er(s), increase area of duct work by 25% to compensate for re-
strictions in air movement.

Venting

To reduce the risk of fire due to increased static
pressure, we do not recommend installation of in-
line secondary lint filters or lint collectors. If secon-
dary systems are mandated, frequently clean the
system to assure safe operation.
IMPORTANT: Installing in-line filters or lint collectors
will cause increased static pressure. Failure to main-
tain the secondary lint system will decrease tumble
dryer efficiency and may void machine warranty.
40
Exhaust Requirements
2
2
[cm
]
Opening
110 [710]
144 [930]
120 [775]
220 [1,420]
180 [1,160]
288 [1,860]
WARNING
Part No. 70686701ENR4
W749