Piping Recommendations

Trap each steam coil individually. Always keep the trap clean
and in good working condition.
When tumble dryer is on the end of a line of equipment, ex-
tend header at least 4 feet [1.2 m] beyond tumble dryer. Install
shut-off valve, union, check valve and bypass trap at end of
line. If gravity return to boiler, omit trap.
Insulate steam supply and return lines for safety of operator
and safety while servicing tumble dryer.
All system components must have a 125 psig [8.6
bar] working pressure. Shut-off valves must be in-
stalled upstream of the steam solenoid valve and
downstream of each steam trap so components can
be isolated for maintenance or emergency purposes.
All components (solenoid valve, traps) must be sup-
ported to minimize loads on the tumble dryer steam
coil connections.
Installing Steam Trap and Making
Condensate Return Connections
The steam trap must be installed and the coil outlet connections
must be connected to the condensate return lines. The following
steps outline the procedure for installing the steam trap and con-
necting the condensate return lines. Refer to Figure 1 for typical
installations.
1. Use flexible lines between steam inlet solenoid and steam
coils, as well as outlet between steam coil and traps.
2. If necessary, install a strainer at the end of each flexible hose.
3. Install a steam trap to each strainer.
IMPORTANT: Steam trap must be installed a mini-
mum of 18 inches [460 mm] recommended below
the steam coil outlet connections.
4. Install a shut-off valve to each steam trap.
5. Connect to the condensate return lines.
©
Published by permission of the copyright owner -
DO NOT COPY or TRANSMIT
Steam Pressure
PSI [bar]
80-125 [5.5-8.6]
WARNING
Minimum Supply Pipe
Diameter
3/4 NPT
Table 33
6. For steam solenoid valve wiring connections, refer to Wiring
Diagram supplied with tumble dryer.
W701R1
79
Steam Requirements
Steam Trap Size*
Pounds Condensate/
Hour [Kilograms Con-
densate/Hour]
140 [63.5]