27 kW Standard Line 055 Series Electric Models
Voltage Code
Voltage
D
200-208
E
230-240
F
200-208
G
230-240
H
380
J
400-415
K
440
L
460-480
18 kW Eco Line 055 Series Electric Models
Voltage Code
Voltage
D
200-208
E
230-240
F
200-208
G
230-240
H
380
©
Published by permission of the copyright owner -
DO NOT COPY or TRANSMIT
Cycle
Phase
50-60
1
50-60
1
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
Table 31
Cycle
Phase
50-60
1
50-60
1
50-60
3
50-60
3
50-60
3
Table 32 continues...
Wire
Full Load
Amps
Refer to Fig-
133
ure 22
Refer to Fig-
116
ure 22
L1, L2, L3
78
and ground
L1, L2, L3
67
and ground
L1, L2, L3
42
and ground
L1, L2, L3
39
and ground
L1, L2, L3
37
and ground
L1, L2, L3
34
and ground
Wire
Full Load
Amps
Refer to Fig-
90
ure 22
Refer to Fig-
78
ure 22
L1, L2, L3
53
and ground
L1, L2, L3
47
and ground
L1, L2, L3
29
and ground
75
Electrical Requirements
Recommend-
Wire Size
ed Circuit
AWG [mm
2
Breaker Rat-
]
ing Amps
175
2/0 [70]
150
1/0 [50]
100
3 [26.7]
90
3 [26.7]
60
6 [16]
50
8 [10]
50
8 [10]
45
8 [10]
Recommend-
Wire Size
ed Circuit
AWG [mm
2
Breaker Rat-
]
ing Amps
125
1 [35]
100
3 [26.7]
70
4 [25]
60
6 [16]
40
8 [10]
Part No. 70686701ENR4