Gas Pipe Size Required for 1000 BTU Natural Gas (Standard Conditions) at Upstream Pressure — 2.0 ± 0.4
PSI [138 ± 28 mbar, 13.7 ± 2.7 kPa]
Equivalent Length
25 feet [7.6
m]
Gas Appli-
Based on 1 PSI Pressure Drop for Length Given
ances Total
BTU/hr.
Sizes shown in Gas Pipe Nominal Size (NPT)
1,700,000
3/4
1,800,000
3/4
1,900,000
3/4
2,000,000
3/4
2,200,000
3/4
2,400,000
1
2,600,000
1
2,800,000
1
3,000,000
1
For L.P. Gas, correct the total Btu/hr by multiplying it by 0.6. The answer is the equivalent Btu on the above chart.
©
Published by permission of the copyright owner -
DO NOT COPY or TRANSMIT
50 feet
75 feet
[15.2 m]
[22.9 m]
1
1
1
1
1
1
1
1
1
1
1
1
1
1-1/4
1
1-1/4
1
1-1/4
Table 16
57
100 feet [30
125 feet [38
m]
m]
1
1
1
1
1
1
1
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
Gas Requirements
150 feet [46
m]
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
1-1/2