E
230-240
F
200-208
G
230-240
H
380
J
400-415
K
440
L
460-480
12 kW Eco Line 035 Series Electric Models
Voltage Code
Voltage
D
200-208
E
230-240
F
200-208
G
230-240
H
380
J
400-415
K
440
L
460-480
©
Published by permission of the copyright owner -
DO NOT COPY or TRANSMIT
50-60
1
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
Table 27
Cycle
Phase
50-60
1
50-60
1
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
50-60
3
Table 28
Refer to Fig-
102
ure 22
L1, L2, L3
69
and ground
L1, L2, L3
59
and ground
L1, L2, L3
37
and ground
L1, L2, L3
34
and ground
L1, L2, L3
32
and ground
L1, L2, L3
30
and ground
Wire
Full Load
Amps
Refer to Fig-
60
ure 22
Refer to Fig-
52
ure 22
L1, L2, L3
36
and ground
L1, L2, L3
31
and ground
L1, L2, L3
19
and ground
L1, L2, L3
18
and ground
L1, L2, L3
17
and ground
L1, L2, L3
15
and ground
73
Electrical Requirements
150
1/0 [50]
90
3 [26.7]
80
4 [25]
50
8 [10]
45
8 [10]
40
8 [10]
40
8 [10]
Recommend-
Wire Size
ed Circuit
AWG [mm
2
Breaker Rat-
]
ing Amps
80
4 [25]
70
4 [25]
45
8 [10]
40
8 [10]
25
10 [6]
25
10 [6]
25
10 [6]
20
12 [4]
Part No. 70686701ENR4