STXPNS001 Devices on a PROFINET subnet must have unique names. The device names
must satisfy the following DNS naming conventions:
Device names are assigned to PROFINET IO device when the device is being set up and
placed in operation for the first time ("commissioned").
The default name is "STXPNS001-SW".
If several devices of the same type are arranged on the same PROFINET IO system, then
PME/ Programing software automatically adds sequential number to the name from the GSD
file. In this case, the second device has the extension "-1", the third one has the extension "-
2", and so on.
■
Communication Speed Setting
GFK-2746B
PACSystems* RSTi PROFIBUS and PROFINET Network Adapter–August 2013
Names are limited to a total of 127 characters (letters, numbers, dashes or dots).
Any component part (that is, a character string between two dots) of the device name
may only be up to 63 characters long.
Names cannot contain any special characters such as umlauts, parentheses,
underscores, forward or backward slashes, empty spaces, and so on. The dash is
the only special character allowed.
Names must not begin or end with the "-" or "." characters.
Names must not have the format n.n.n.n (where n = 0...999).
The device name must not start with numbers.
Names must not begin with the character sequence "port-xyz-" (where x, y, z = 0...9).
If you want to change the IP address in non-volatile memory, please refer to
Configuration section for more details.
Refer to GEIP PROFINET master module settings to change the communication
speed (GE-IP PROFINET Controller User Manual- GFK-2571).