Chapter 3. PROFIBUS Network Adapters

Error Decode (PROFIBUS-DP Extensions to EN 50170)

3.3.8

Error Code_1 (PROFIBUS-DP Extensions to EN 50170)

3.3.9
64
0~127 : Reserved
128 : DPV1
129~253 : Reserved
254 : FMS
255 : HART
Bit
7
6
Error Class
0xA : Application class
Error Class
0xB : Access class
Error Class
0xC : Resource class
Error Class
0xD : STXPBS001 Specific
Class
PACSystems* RSTi PROFIBUS and PROFINET Network Adapter–August 2013
5
4
3
Error code
Error code
Error code
Error code
2
1
0: Read Error
1: Write Error
2: Module Failure
3 ~7: Reserved
8: Version conflict
9: Feature not supported
10~15: User specific
0: Invalid index
1: Write length error
2: Invalid slot
3: Type conflict
4: Invalid area
5: state conflict
6: access denied
7: invalid range
8: invalid parameter
9: invalid type
10~15: User specific
0: read constrain conflict
1: Write constrain conflict
2: Resource busy
3 Resource unavailable
4 ~7: Reserved
8~15: User specific
1: Slot Parameter write
error
2: Read memory error
3: Write memory error