3.2
Optionally: Setting up the T station with the help of the wizard
The station wizard helps you to carry out several steps when configuring a CPU 31xT in one
work cycle. You have the following options:
● Using the station wizards
● Not using the station wizards
Procedure
Step
Activity
1
Set up a new project in the SIMATIC Manager (e.g. "Getting Started CPU 317T").
2
Select the Insert > Station > SIMATIC T Station menu command.
The "Set up T station" dialog box opens.
Select the following settings in the fields:
"CPU type": CPU317T-2 DP
"Generate Technology System Data" option activated
"MPI/DP": New, type MPI, transmission rate 1.5 Mbps
"PG/PC": Not used
Carry out the settings in all other fields.
If required, press the button "Help" to obtain additional information.
CPU 317T-2 DP: Controlling a SINAMICS S120
Getting Started, 03/2008, A5E00480391-03
Carry out the following described steps and then continue with learning unit "6th step".
Do not carry out the following described steps, instead, continue with the learning unit
"2nd step".
3.2 Optionally: Setting up the T station with the help of the wizard
Learning units
13