Step
Activity
41
In the "SINAMICS_S120 – Configuration" dialog box, set both message frame types to "SIEMENS telegram
105" and then click the "Align with HW Config" button in order to establish message addresses in the
columns "Input data" and "Output data".
42
Check to see if valid addresses have been entered for all messages and close the "SINAMICS_S120 –
Configuration" dialog box by clicking on "Close".
CPU 317T-2 DP: Controlling a SINAMICS S120
Getting Started, 03/2008, A5E00480391-03
3.10 9. Step: Configuration of the SINAMICS drive with S7T Config
Result