3.10 9. Step: Configuration of the SINAMICS drive with S7T Config
Step
Activity
23
In the project navigator, open the tree structure SIMATIC 300(1) > Technology > SINAMICS_S120 >
Drives > Servo_03.
Right-click to open the context menu and select Expert > Expert list.
24
Select parameter "p210" and enter "345".
The Smart Line Module and the Motor Module of the SINAMICS S120 training case have been especially
equipped for operation on a 230 V system. For this reason, "Parameter p210" of the connected drives must
be set to the following value, which differs from the factory settings:
p210 = 345 V device connection voltage SERVO/VECTOR
The setting of "parameter p210 = 345 V" cannot be calculated by the SINAMICS operating system and is
pre-assigned for the error-free operation of the SINAMICS S120 training case on the 230 V system.
40
Result
CPU 317T-2 DP: Controlling a SINAMICS S120
Getting Started, 03/2008, A5E00480391-03