Section 2
DNP3 data mappings
2.3.6.18
Table 36:
LD0.FRPFRQ2 Frequency protection (2)
IEC 61850 name
LD0.FRPTRC2
.Str.general
LD0.FRPTOF2
.Op.general
LD0.FRPTUF2
.Op.general
LD0.FRPFRC2
.Op.general
2.3.6.19
Table 37:
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
IEC 61850 name
LD0.HAEFPTOC1
.Op.general
.Str.general
2.3.6.20
Table 38:
LD0.INPHAR1 Three-phase inrush detection
IEC 61850 name
LD0.INPHAR1
.Str.general
2.3.6.21
Table 39:
LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
IEC 61850 name
LD0.NSPTOC1
.Op.general
.Str.general
26
LD0.FRPFRQ2 Frequency protection (2)
SA name
START
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
SA name
OPERATE
START
LD0.INPHAR1 Three-phase inrush detection
SA name
-
LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
SA name
OPERATE
START
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Stage operate
Stage start
Description
General start
Description
Stage operate
Stage start
Recloser Protection and Control RER615
1MRS757823 A
Values
1=Start
1=Operate
1=Operate
1=Operate
Values
1=Operate
1=Start
Values
1=Start
Values
1=Operate
1=Start
Point List Manual