1MRS757823 A
2.3.7.2
Table 59:

LD0.DARREC1 Autorecloser

IEC 61850 name
LD0.DARREC1
.PrgRec1.stVal
.PrgRec2.stVal
.PrgRec3.stVal
.PrgRec4.stVal
.PrgRec5.stVal
.PrgRec.stVal
.CBManCls.stVal
.LO.stVal
.UnsRec.stVal
.InBlkThm.stVal
.RdyRec.stVal
.ActRec.stVal
.PrgDsr.stVal
.PrgCutOut.stVal
.FrqOpAlm.stVal
.RclTmStr.stVal
.ProCrd.stVal
.Op.general
.OpOpn.general
.UnsCBCls.stVal
.WtMstr.stVal
2.3.7.3
Table 60:

DR.RDRE1 Disturbance recorder

IEC 61850 name
DR.RDRE1
.RcdMade.stVal
Recloser Protection and Control RER615
Point List Manual
LD0.DARREC1 Autorecloser
SA name
INPRO_1
INPRO_2
INPRO_3
INPRO_4
INPRO_5
INPRO
MAN_CB_CL
LOCKED
UNSUC_RECL
-
READY
ACTIVE
DISCR_INPRO
CUTOUT_INPRO
FRQ_OP_ALM
-
-
CLOSE_CB
OPEN_CB
UNSUC_CB
CMD_WAIT
DR.RDRE1 Disturbance recorder
SA name
Description
AR 1st reclose
AR 2nd reclose
AR 3rd reclose
AR 4th reclose
AR 5th reclose
AR in progress
CB manually closed
Lockout status
Reclose fail status
Thermal block (status)
Ready reclose status
Active reclose status
Discrimination time in p.
Cutout time in progress
Frequent operation alarm
Reclaim time started
Protection coordination
Operate (close XCBR)
Operate (open XCBR)
CB closing failed
Master signal to follower
Description
DR recording made
Section 2
DNP3 data mappings
Values
1=In progress
1=In progress
1=In progress
1=In progress
1=In progress
1=In progress
1=CB closed
1=Lockout
1=Failed
1=Block
1=Ready
1=Active
1=In progress
1=In progress
1=Alarm
1=Started
1=In progress
1=Close CB
1=Open CB
1=Failed
1=Signal
Values
1=Made
31