Ld0.Vsmsqi2 Sequence Of Voltage Measurement (2); Ld0.Pemmtr1 Power Measurement And Accumulated Power Values; Ld0.Fmmxu1 Frequency Measurement; Ld0.Ledggio1 Lhmi Led Indications (3 States) - ABB Relion 615 Series Manual

Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS757823 A
2.5.3.7
Table 105:

LD0.VSMSQI2 Sequence of voltage measurement (2)

IEC 61850 name
SA name
LD0.VSMSQI2
.SeqV.c1.cVal.mag
.SeqV.c2.cVal.mag
.SeqV.c3.cVal.mag
2.5.3.8
Table 106:

LD0.PEMMTR1 Power measurement and accumulated power values

IEC 61850 name
SA name
LD0.PEMMTR1
.DmdVArh.actVal
.DmdWh.actVal
.SupVArh.actVal
.SupWh.actVal
.TotPF.instMag
.TotW.instMag
.TotVA.instMag
.TotVAr.instMag
2.5.3.9
Table 107:

LD0.FMMXU1 Frequency measurement

IEC 61850 name
SA name
LD0.FMMXU1
.Hz.mag
2.5.3.10
Table 108:

LD0.LEDGGIO1 LHMI LED indications (3 states)

IEC 61850 name
SA name
LD0.LEDGGIO1
.ISCSO1.stVal
.ISCSO2.stVal
Table continues on next page
Recloser Protection and Control RER615
Point List Manual
LD0.VSMSQI2 Sequence of voltage measurement (2)
Description
Sequence of voltages
I1_DB
-Positive magnitude
I2_DB
-Negative magnitude
I3_DB
-Zero magnitude
LD0.PEMMTR1 Power measurement and accumulated power values
Description
ER_RV_ACM
Forward reactive energy
EA_RV_ACM
Forward active energy
ER_FWD_ACM
Reverse reactive energy
EA_FWD_ACM
Reverse active energy
PF_INST
Average power factor
P_INST
Active power
S_INST
Apparent power
Q_INST
Reactive power
LD0.FMMXU1 Frequency measurement
Description
-
Frequency value
LD0.LEDGGIO1 LHMI LED indications (3 states)
Description
-
LED 1 state
-
LED 2 state
DNP3 data mappings
Values
S
Arg 1,2,3,4
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
Values
S
Arg 1,2,3,4
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
0...1e10
R
0,1E10,0,1E10
-1...1
R
-1,1,-100,100
0...999999
R
0,999999,0,999999
0...999999
R
0,999999,0,999999
0...999999
R
0,999999,0,999999
Values
S
Arg 1,2,3,4
35...75 [Hz]
R
35,75,3500,7500
Values
S
Arg 1,2,3,4
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
Section 2
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents