Sensors And Monitoring Functions; Ld0.Sscbr1 Circuit-Breaker Condition Monitoring; Ld0.Tcsscbr1 Trip Circuit Supervision (1); Ld0.Tcsscbr2 Trip Circuit Supervision (2) - ABB Relion 615 Series Manual

Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS757823 A
IEC 61850 name
.OpEx.general
.OpIn.general
.Str.general
2.3.3
2.3.3.1
Table 8:

LD0.SSCBR1 Circuit-breaker condition monitoring

IEC 61850 name
.APwrAlm.stVal
.APwrLO.stVal
.CBLifAlm.stVal
.ClsAlm.stVal
.LonTmAlm.stVal
.OpnAlm.stVal
.OpNumAlm.stVal
.OpNumLO.stVal
.PresAlm.stVal
.PresLO.stVal
.SprChaAlm.stVal
2.3.3.2
Table 9:

LD0.TCSSCBR1 Trip circuit supervision (1)

IEC 61850 name
LD0.TCSSCBR1
.CirAlm.stVal
2.3.3.3
Table 10:

LD0.TCSSCBR2 Trip circuit supervision (2)

IEC 61850 name
LD0.TCSSCBR2
.CirAlm.stVal
Recloser Protection and Control RER615
Point List Manual
SA name
TRBU
TRRET
CB_FAULT_AL

Sensors and monitoring functions

LD0.SSCBR1 Circuit-breaker condition monitoring
SA name
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
TRV_T_CL_ALM
MON_ALM
TRV_T_OP_ALM
OPR_ALM
OPR_LO
PRES_ALM
PRES_LO
SPR_CHR_ALM
LD0.TCSSCBR1 Trip circuit supervision (1)
SA name
ALARM
LD0.TCSSCBR2 Trip circuit supervision (2)
SA name
ALARM
Description
Failure ext.trip
Operate, re-trip
Start, timer running
Description
Iyt alarm
Iyt lockout
CB lifetime alarm
Cls travel time alarm
CB inactive alarm
Cls travel time alarm
CB operations alarm
CB operations lockout
Low pressure alarm
Low pressure lockout
Spring charge time alarm
Description
Supervision alarm
Description
Supervision alarm
Section 2
DNP3 data mappings
Values
1=Failure
1=Operate
1=Start
Values
1=Alarm
1=Lockout
1=Alarm
1=Alarm
1=Alarm
1=Alarm
1=Alarm
1=Lockout
1=Alarm
1=Lockout
1=Alarm
Values
1=Alarm
Values
1=Alarm
19