Protection Functions; Ld0.Ledptrc1 Global Protection Signals; Ld0.Trpptrc1 Global Conditioning (1); Ld0.Trpptrc2 Global Conditioning (2) - ABB Relion 615 Series Manual

Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 2
DNP3 data mappings
2.3.6
2.3.6.1
Table 19:

LD0.LEDPTRC1 Global protection signals

IEC 61850 name
LD0.LEDPTRC1
.Op.general
.Op.phsA
.Op.phsB
.Op.phsC
.Str.general
.Str.phsA
.Str.phsB
.Str.phsC
2.3.6.2
Table 20:

LD0.TRPPTRC1 Global conditioning (1)

IEC 61850 name
LD0.TRPPTRC1
.Op.general
.Tr.general
2.3.6.3
Table 21:

LD0.TRPPTRC2 Global conditioning (2)

IEC 61850 name
.Op.general
.Tr.general
2.3.6.4
Table 22:

LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1

IEC 61850 name
LD0.DEFHPTOC1
.Op.general
.Str.general
22

Protection functions

LD0.LEDPTRC1 Global protection signals
SA name
-
-
-
-
-
-
-
-
LD0.TRPPTRC1 Global conditioning (1)
SA name
-
-
LD0.TRPPTRC2 Global conditioning (2)
SA name
-
-
LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1
SA name
OPERATE
START
Description
Global protection signals
-General Operate
-phsA Operate
-phsB Operate
-phsC Operate
-General Start
-phsA Start
-phsB Start
-phsC Start
Description
Operate input signal
Trip output signal
Description
Operate input signal
Trip output signal
Description
High stage (1)
-Operate
-Start
Recloser Protection and Control RER615
1MRS757823 A
Values
1=Operate
1=Operate
1=Operate
1=Operate
1=Start
1=Start
1=Start
1=Start
Values
1=Operate
1=Trip
Values
1=Operate
1=Trip
Values
1=Operate
1=Start
Point List Manual