Metering And Measurand Functions; Ld0.Cmmxu1 Phase Currents (1); Ld0.Rescmmxu1 Residual Current (1); Ld0.Csmsqi1 Sequence Of Currents - ABB Relion 615 Series Manual

Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS757823 A
2.5.3
2.5.3.1
Table 99:

LD0.CMMXU1 Phase currents (1)

IEC 61850 name
SA name
LD0.CMMXU1
.A.phsA.instCVal.mag
.A.phsB.instCVal.mag
.A.phsC.instCVal.mag
2.5.3.2
Table 100:

LD0.RESCMMXU1 Residual current (1)

IEC 61850 name
SA name
LD0.RESCMMXU1
.A.res.instCVal.mag
2.5.3.3
Table 101:

LD0.CSMSQI1 Sequence of currents

IEC 61850 name
SA name
LD0.CSMSQI1
.SeqA.c1.instCVal.mag
.SeqA.c2.instCVal.mag
.SeqA.c3.instCVal.mag
2.5.3.4
Table 102:

LD0.VMMXU1 Voltage measurement

IEC 61850 name
SA name
LD0.VMMXU1.PhV
.phsA.cVal.mag
.phsB.cVal.mag
.phsC.cVal.mag
LD0.VMMXU1.PPV
Table continues on next page
Recloser Protection and Control RER615
Point List Manual

Metering and measurand functions

LD0.CMMXU1 Phase currents (1)
Description
Phase-to-ground current
I_INST_A
-phsA magnitude
I_INST_B
-phsB magnitude
I_INST_C
-phsC magnitude
LD0.RESCMMXU1 Residual current (1)
Description
I0_INST
Residual current
LD0.CSMSQI1 Sequence of currents
Description
Sequence of currents
I1_INST
-Positive magnitude
I2_INST
-Negative magnitude
I3_INST
-Zero magnitude
LD0.VMMXU1 Voltage measurement
Description
Phase-to-ground voltage
U_DB_A
-phsA magnitude
U_DB_B
-phsB magnitude
U_DB_C
-phsC magnitude
Phase-to-phase voltage
DNP3 data mappings
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
Section 2
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents