CTRL.LLN0 Local remote station off

IEC 61850 name
SA name
CTRL.LLN0
.LocRem.stVal
2.5.1.2
Table 92:

LD0.LPHD1 System values

IEC 61850 name
SA name
LD0.LPHD1
.NumCmpChg.stVal
.NumPwrUp.stVal
.PhyHealth1.stVal
.PhyHealth2.stVal
.WacTrg.stVal
.WrmStr.stVal
2.5.1.3
Table 93:

LD0.DNPGGIO1 Active parameter setting group

IEC 61850 name
SA name
LD0.DNPGGIO1
.ActSG.stVal
Recloser Protection and Control RER615
Point List Manual
Column name
Description
Values
The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S
Scaling type selected as default. Default "R" means ratio scaling. See the DNP3
communication protocol manual for details.
Arg 1, 2, 3, 4
Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP3 communication protocol manual for details.

System functions

CTRL.LLN0 Local remote station off
Description
Off=0; Loc=1; Rem=2;
-
Station=3
LD0.LPHD1 System values
Description
-
Num.of comp. changes
-
Num.of power ups
Warning
Warning code
Internal Fault
Internal fault code
-
Num.of watchdog resets
-
Num.of warm starts
LD0.DNPGGIO1 Active parameter setting group
Description
-
Active setting group
DNP3 data mappings
Values
S
Arg 1,2,3,4
0...3
R
0,3,0,3
Values
S
Arg 1,2,3,4
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
Values
S
Arg 1,2,3,4
1...6
R
1,6,1,6