In a Report Control Block (RCB), the data are pushed by the server on a trigger. The trigger
support several options:
3.3.6

Read Variables of Each IED

Use either of the two options below to read variables of each IED.
a.
b.
Configuration
TrgOp data-change
The enabling of this option will ensure that data will be available on Data value
change.
TrgOp quality-change
The enabling of this option will ensure that data will be available Quality change.
TrgOp data-update
The enabling of this option will ensure that data will be available only on Timestamp
change.
TrgOp integrity
The enabling of this option will ensure that data will be available on integrity poll as
defined in "bufTm" in respective RCB.
TrgOp general-interrogation
The enabling of this option will enable general interrogation on request by the client
(GI).