Faults Rep Faults Reported to the RX3i I/O Fault Table

The following ECM850-related faults are reported in the I/O Fault Table of the RX3i CPU, in
addition to being listed in the ECM850's Local Log Table.
Faults Reported to the RX3i I/O Fault Table
Group- Category-
Type- Description
3-2-0-0
3-35-1-0
3-68-1-0
3-68-2-0
3
The network connection issue might be in the interconnecting network between the controller and the device, and not necessarily at the
device itself. In a network with a large number of clients, storing a configuration that causes all clients to reconfigure (for example, changing
the Domain Name) may generate a large number of Loss/Addition of Device faults. This is expected behavior, and all devices should
thereafter automatically return to operation.
Diagnostics
Description
An error occurred in an operating system request. This is an internal software error.
"LAN system-software fault; resuming"
An error occurred in registering for configuration. This is an internal software error.
"LAN system-software fault; resuming"
An error occurred in retrieving configuration. This is an internal software error.
"LAN system-software fault; resuming" Internal configuration error.
"LAN system-software fault; resuming" Internal messaging error.
"LAN system-software fault; resuming"
Error in producing tally output.
"LAN system-software fault; resuming"
This is not an error but represents the change of State of Synchronization
Description
Loss of Device
Expected SFP is
missing.
Unsupported SFP
detected.
Invalid SFP
detected.
Cause
Recommended
3-2-0-0
If this is unexpected
operation, either re-
connect missing IED
on the network, or
remove the device
from the ECM850's
configuration.
SFP configured for a
Insert SFP into port of
port on the ECM850 is
ECM850 to match
not physically present.
configuration stored
to the ECM850 or
remove the SFP from
configuration.
An unsupported (non-
The installed SFP is not
Ethernet) SFP is
supported, replace
physically connected
with supported SFP
to a ECM850 port.
An invalid (non-
The installed SFP is
functional) SFP is
invalid, replace with a
supported SFP
Chapter 5
Oct 2019