Removing the Backplane Knockout

The ECM850 must be installed in the main (CPU) rack of an RX3i system, using a Universal
Backplane such as IC695CHS007, CHS012 or CHS016.
The back of the ECM850 has an exposed heat sink and backplane connector. Before
inserting the module into the backplane, remove the plastic knockout in the slot where the
module will be placed. The installation slot must match the slot that is selected in the
module's hardware configuration.
Figure 11
2.4.2

Module Insertion

Figure 12
Installation
RX3i rack power may be off or on (see Section 2.4.4, Hot Insertion and Removal).
Holding the module firmly, align the module with the correct slot and connector.
Engage the module's rear pivot hook in the notch on the top of the backplane (1).
Swing the module down until the module's connector engages the backplane
connector (2).
Visually inspect the module to be sure it is properly seated.
Turn the heat sink screw on the front of the module several turns into the threaded
hole in the backplane using a flat-tip screwdriver (3), but do not tighten.