ECM850 Faults in the RX3i Fault Tables

The ECM850 logs all (Local, Controller, I/O) faults in its Local Log. In addition, it logs
Controller and I/O faults in the corresponding RX3i CPU's fault tables (the Controller Fault
Table or the I/O Fault Table).
5.6.1

Clearing the RX3i Fault Tables

Clearing one or both of the RX3i CPU's fault tables has no effect on the ECM850's Local Log
table. The ECM850's Local Log can only be cleared from its Command Line Interface.
Likewise, clearing one or both of the RX3i CPU's fault tables has no effect on the diagnostic
conditions maintained by any IO-Device.
5.6.2

Faults Reported to the RX3i Controller Fault Table

The following ECM850 related faults are reported in the Controller Fault Table of the RX3i
CPU, in addition to being listed in the ECM850's Local Log Table.
Faults Reported to the RX3i Controller Fault Table
Group- Error
Code
11-84
Diagnostics
Description
Cause
Configured SFP
SFP configured for a port
mismatch
on the ECM850 does not
detected.
match what is physically
present on the ECM850.
Chapter 5
Oct 2019
Recommended Action
The SFP present should operate
properly in the presence of this
fault. However, to eliminate
the fault, either update
configuration to match the
actual SFP type in use or replace
the SFP in use with the same
type of SFP configured.