6 Related Drive Parameters
No.
Name
(Hex.)
b1-01
Frequency
Reference
(0180)
Selection 1
b1-02
Run Command
Selection 1
(0181)
E2-04
Motor Pole
Count
(0311)
F6-01
Communication
Error Selection
(03A2)
38
Description
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• Set b1-02 = 3 [Run Command Selection 1 = Option
PCB] to use the master device and serial
communications to start and stop the drive. Set b1-01 =
3 to use the master device to control the frequency
reference of the drive.
• The default setting is different for different drives. Refer
to the instruction manual of your specific drive for more
information.
Selects the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
Note:
Set b1-02 = 3 to start and stop the drive with the master
device using serial communications. Set b1-01 = 3
[Frequency Reference Selection 1 = Option PCB] to use
the master device to control the frequency reference of the
drive.
Set the number of motor poles described on the motor
nameplate.
Note:
• Relevant for DSP402.
–1000-Series: 2 - 48
–GA500, GA700, GA800, FP605: 2 - 120
• E2-04 is necessary to set up when the Drive Profile DSP
402 objects are used.
Selects drive response when the drive detects a bUS [Option
Communication Error] error during communications with the
option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm - Run at d1-04
5 : Alarm - Ramp Stop
YASKAWA TOEP C730600 85A CANopen Installation Manual
Default
(Range)
1
(0 - 4)
1
(0 - 3)
4
(2 - 48)
1
(0 - 5)