Error Codes 6501 To 6510 - Mitsubishi Electric FX Series Training Manual

Programmable logic controllers
Hide thumbs Also See for FX Series:
Table of Contents

Advertisement

Appendix
Error
Parameter error
A.3.2

Error codes 6501 to 6510

Error
Syntax error
Training Manual GX IEC Developer
Special
Error
Description
Register
Code
0000
No error
6401
Program sum check error
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
D8064
Special unit (BFM) initial value setting,
6406
positioning instruction setting sum
check error
Special unit (BFM) initial value setting,
6407
positioning instruction setting error
6409
Other setting error
Special
Error
Description
Register
Code
0000
Kein Fehler
Incorrect combination of instruction,
6501
device symbol and device number
No OUT T or OUT C before setting
6502
value
No OUT T or OUT C before setting
value
6503
Insufficient number of operands for
an applied instruction
Same label number is used more
than once.
D8065
6504
Same interrupt input or high speed
counter input is used more than
once.
Device number is out of allowable
6505
range.
6506
Invalid instruction
6507
Invalid label number [P]
6508
Invalid interrupt input [I]
6509
Other error
6510
MC nesting number error
Error Code List
Corrective Action
STOP the PLC, and cor-
rectly set the parameters.
Corrective Action
During programming, each
instruction is checked. If a
syntax error is detected,
modify the instruction
correctly.