REMKO Smart Control Touch Operating Manual page 96

For the wsp heat pump range
Hide thumbs Also See for Smart Control Touch:
Table of Contents

Advertisement

REMKO Smart-Control Touch
ID
Description
ID7070 High pressure switch
ID7071 Inverter interlocked
ID7072 Inverter malfunction
ID7073 DLT probe fault
ID7074 Fan malfunction
ID7075 Low pressure
Overheating point
ID7076
undershot
Overheating point
ID7077
exceeded
High pressure malfunc-
ID7078
tion
ID7079 Envelope alarm
High heat gas tempera-
ID7080
ture
ID7081 4-way valve fault
ID7082 Expansion valve fault
ID7083 Fault with probe P1
ID7084 Fault with probe P2
ID7085 Fault with probe T1
ID7086 Fault with probe T2
ID7087 Fault with probe T3
ID7088 Fault with probe T4
ID7089 Fault with probe T5
ID7090 Fault with probe T7
Inverter communication
ID7091
error
ID7092 High pressure switch
ID7093 Inverter interlocked
ID7094 Inverter malfunction
ID7095 DLT probe fault
ID7096 Anti-freeze protection
Flow switch (contact
ID7097
open)
Logic error source cir-
ID7098
cuit
96
Desig. Details
HP 1
The high pressure switch was triggered
HP 1
Inverter interlocked
HP 1
Inverter malfunction
HP 1
Temperature probe DLT was not detected
HP 2
Fan malfunction
HP 2
Pressure transducer P1
HP 2
Temperature below overheating point for too long
HP 2
Temperature above overheating point for too long
HP 2
Pressure transducer P2
HP 2
The compressor ran outside its usable limits for too long
HP 2
The maximum hot gas temperature has been exceeded
HP 2
Pressure difference too low
HP 2
The expansion valve was not detected
HP 2
Pressure transducer P1 was not detected
HP 2
Pressure transducer P2 was not detected
HP 2
Temperature probe T1 was not detected
HP 2
Temperature probe T2 was not detected
HP 2
Temperature probe T3 was not detected
HP 2
Temperature probe T4 was not detected
HP 2
Temperature probe T5 was not detected
HP 2
Temperature probe T7 was not detected.
HP 2
Communication with the inverter was interrupted
HP 2
The high pressure switch was triggered
HP 2
Inverter interlocked
HP 2
Inverter malfunction
HP 2
Temperature probe DLT was not detected
The anti-freeze protection in the heat pump's heat exchanger
was triggered due to a return temperature that is too low. After
HP 2
rectifying the cause of the error, reset the error in (Expert/
Settings/Heat pump/Basic settings) and, if necessary, de-ener-
gise the outdoor unit
Open contact of the flow switch (jumper plug) during defrost /
cooling mode
Logic error source circuit - medium flow rate in the source cir-
cuit with closed valve