Operating mode
Two operating modes are available:
1.
Bivalent alternative
2.
Monoenergetic
Menu item
Operating mode selection
Selection of the auxiliary heat generator:
- Bivalent alternative (heat pump or oil/gas-fired boiler or wall heating)
- Monoenergetic (heat pump and/or Smart Serv electric heating element) according to usable limits
The operating mode of the internal pump in the indoor unit must be defined here in the level "Expert " Set-
tings " Auxiliary heat generator " Internal pump".
Passive cooling
Activation of passive cooling. An additional module for the passive cooling is a prerequisite.
Menu item
Passive cooling
Brine outlet setpoint
Desired brine outlet temperature. The brine pump implements control according to this temperature.
Menu item
Brine outlet setpoint
Anti-freeze protection temperature
The anti-freeze protection function becomes active from this temperature in the brine circuit.
Menu item
Anti-freeze protection temperature
Anti-freeze protection alarm temperature
For frost protection reasons, the heat pump is blocked from this temperature in the brine circuit.
Menu item
Anti-freeze protection alarm tem-
perature
Parameter
Monoenergetic
Bivalent alternative
Parameter
Activated
Deactivated
Parameter
-15 °C - +20 °C
Parameter
-20 °C - +10 °C
Parameter
-25 °C - +5 °C
Factory setting
Monoenergetic
Factory setting
Deactivated
Factory setting
+8 °C
Factory setting
+4 °C
Factory setting
+2 °C
77