ID
Description
ID7261 Fault with probe B1
Outside temperature
ID7262
probe error
Error brine outlet temp.
ID7263
Probe
Inlet temperature probe
ID7264
error
ID7265 Fault with probe B5
ID7266 Fault with probe B6
Outlet temperature
ID7267
probe error
ID7268 Fault with probe B8
Hot gas temperature
ID7269
probe error
Suction gas tempera-
ID7270
ture probe error
High pressure probe
ID7271
error
Low pressure probe
ID7272
error
ID7273 WKF fault code E101
ID7274 WKF fault code E177
ID7275 WKF fault code E221
ID7276 Restart required
ID7278 Low overheating
Low pressure differ-
ID7282
ence
Open contact - internal
ID7283
return temp. probe
Short circuit - internal
ID7284
return temperature
probe
Low suction gas
ID7285
temperature
ID7286 Coding error
Desig. Details
Please check probe and the connection to the inverter board
Outside temperature probe error - please check the outside
µPC
temperature sensor on the inverter board and its connection
Error brine outlet temp. Probe - please check the brine outlet
µPC
temperature probe on the inverter board and its connection
Inlet temperature probe error - please check the inlet tempera-
µPC
ture probe on the inverter board and its connection
Please check probe B5 and the connection to the inverter
board
Please check probe B6 and the connection to the inverter
board
Outlet temperature probe error - please check the outlet tem-
µPC
perature probe on the inverter board and its connection
Please check probe B8 and the connection to the inverter
board
Hot gas temperature probe error - please check the hot gas
µPC
temperature probe on the inverter board and its connection
Suction gas temperature probe error - please check the suc-
µPC
tion gas temperature probe on the inverter board and its con-
nection
High pressure probe error - please check the high pressure
µPC
probe on the inverter board and its connection
Low pressure probe error - please check the low pressure
µPC
probe on the inverter board and its connection
Communication error between com. kit and outdoor unit. F1/F2
twisted or cable break
Compressor stopped due to an emergency stop signal. After
eliminating the cause of the error, the indoor and outdoor units
must be restarted to reset the error
Short circuit or open contact - probe ambient air temperature
motherboard outdoor unit CN43 Pin 1&2
Due to the changed system (setting / coding resistor), the con-
troller has to be restarted - disconnect it from the power supply
for around 10 seconds
The compressor is disabled due to overheating being too low
µPC
The pressure difference in the cooling cycle is too low.
S15
Open contact - internal return temperature probe
S15
Short circuit - internal return temperature probe
The compressor is disabled due to the suction gas tempera-
µPC
ture being too low
A unique unit identifier could not be assigned using the coding
Rc
resistor at the Rc terminal
101