REMKO Smart Control Touch Operating Manual page 81

For the wsp heat pump range
Hide thumbs Also See for Smart Control Touch:
Table of Contents

Advertisement

Standard outside temperature (heating)
The standard outside temperature must be set to the appropriate value for the region. After setting the cor-
rect temperature, this is stored for all activated heating circuits that are to be controlled in accordance with a
heating curve.
Menu item
Standard outside temperature
(heating)
Standard outside temperature (cooling)
The standard outside temperature must be set to the appropriate value for the region. After setting the cor-
rect temperature, this is stored for all activated cooling circuits that are to be controlled in accordance with a
cooling curve.
Menu item
Standard outside temperature
(cooling)
System separation underfloor heating
If system separation (heat exchanger) is used for panel heater operation, the heat loss via the heat
exchanger can be compensated via the activation.
Menu item
System separation underfloor
heating
Parameter
0 °C - -20 °C
Parameter
+30 °C - +40 °C
Parameter
Deactivated
Activated
Factory setting
-10 °C
Factory setting
+36 °C
Factory setting
As required