Operating manual REMKO Smart WP MANAGER Smart Control for SQW 400 Manual for experienced specialists Read the instructions prior to performing any task! 0161-2017-09 Edition 1, en_GB...
Page 2
Read these operating instructions carefully before commis- sioning / using this device! These instructions are an integral part of the system and must always be kept near or on the device. Subject to modifications; No liability accepted for errors or mis- prints! Translation of the original operating manual...
Table of contents Safety and usage instructions......................4 1.1 General safety notes........................4 1.2 Identification of notes........................4 1.3 Personnel qualifications........................4 1.4 Dangers of failure to observe the safety notes................4 1.5 Safety-conscious working....................... 4 1.6 Safety notes for the operator......................5 1.7 Safety notes for installation, maintenance and inspection..............
REMKO Smart WP MANAGER Safety and usage instructions CAUTION! This combination of symbol and signal word 1.1 General safety notes warns of a potentially hazardous situation, which if not avoided may cause injury or mate- Carefully read the operating manual before com- rial and environmental damage.
The setup, connection and operation of the plete and return the "certificate of warranty" to units and its components must be undertaken REMKO GmbH & Co. KG at the time when the in accordance with the usage and operating units are purchased and commissioned.
REMKO Smart WP MANAGER 1.11 Transport and packaging Operation - General The devices are supplied in a sturdy shipping con- 2.1 Design and functions tainer or inside the heat pump casing. Please check the equipment immediately upon delivery Overview of the controls...
Page 7
NOTICE! Fig. 4: Calling up the main menu The settings in expert mode may only be con- figured by REMKO-authorised installers! Selecting a menu item Select the menu item "Settings" (for example) and There are two different authorisation levels for the then confirm your selection with "OK"...
Page 8
REMKO Smart WP MANAGER Confirm the selection "Language/Time" with "OK" (right softkey). You are now on the parameter menu of the "Language/Time" folder. Time: : 00 Language / Time Fig. 9: Selecting a parameter 2 Fig. 7: Language/Time Changing the parameter Turn the rotary knob to set the number of hours.
Operation - User level Exiting the menu Provided that no parameter has been selected, the 3.1 Menu structure of the controller label "Back" appears on the display, over the left softkey. Press the left softkey multiple times to get The following information is primarily directed at back to the home screen.
Page 10
REMKO Smart WP MANAGER Overview of the menus (User level) Favourites LEVEL 0 3D house Hot water Room climate menu Main menu Chimney LEVEL 1 Information Settings Messages sweep Basic Basic Error messages LEVEL 2 Mode information settings warnings Domestic...
Page 11
"3D house" animation Explanation of operating statuses: Once the Smart Control commissioning wizard has Circuit is in operation been completed, you will see the home screen with Hot water or heating is being heated the 3D house. Pressing the left softkey starts the animation.
Page 12
REMKO Smart WP MANAGER Pressing the right softkey zooms in on the indi- Favourites menu: for the user vidual components in the house and the current Using the rotary knob (turning it clockwise) you can parameters, such as storage tank and collector access other views.
Page 13
Room climate One-off hot water/party mode Colder/Warmer can be used to adjust the temper- Activating Party mode (select with the right ature of the heating (set with the left softkey, then softkey) causes the next window of time with confirm with "OK"). If the room temperature is too reduced heating to be disregarded, so that the low, the room thermostat (on the heater) should heating runs in normal mode again.
Page 14
REMKO Smart WP MANAGER You can use the right softkey to activate an "away savings period". The system will then function in reduced savings specifies how much CO emissions mode until the right softkey is pressed again. have been avoided. The calculation of CO...
Page 15
"Main menu" menu item Pressing the Menu key takes you to the main menu. There is an expert mode and a user mode. The two authorisation levels are identified by icons. Some menu items and parameters are only visible in expert mode.
Page 16
REMKO Smart WP MANAGER "Information" menu item - User This menu contains information about the current operating status of the system. The menu is opened with the key on the right. Pressing the left-hand key allows you to jump up a level in the menu structure again. By turning the rotary knob, you can select another menu item (for instance "Settings").
Page 17
"Information" menu item (continued) - User Authorisa- Level 2 Level 3 menu item Info tion level menu item HW request HW storage tank set temp. HW storage tank actual temp. S03 HW storage tank actual temp. S04 Hot water energy Hot water Hygiene function Circulation request S05...
Page 18
REMKO Smart WP MANAGER "Information" menu item (continued) - User Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Set temp. Actual temp. Room set temp. 1st mixed cycle Room actual temp. Room humidity Dew point...
Page 19
"Information" menu item (continued) - User Authorisa- Level 2 Level 3 menu item Level 4 menu item Info tion level menu item Heat pump status Remaining idle time Compressor status Defrost status Fault status 1. Heat pump Enable signal Disable compressor Heat pump mode Disable signal S40 Enable hot water...
Page 20
REMKO Smart WP MANAGER "Information" menu item (continued) - User Authorisa- Level 2 Level 3 menu item Level 4 menu item Info tion level menu item Therm. power, heat pump Therm. energy, heat pump Heat pump elec. power Heat pump Heat pump elec.
Page 21
"Settings" menu item - User In this menu you can configure the settings. For example, you can adjust hot water and heating tempera- tures or change time settings. The menu is opened with the key on the right. Pressing the left-hand key allows you to jump up a level in the menu structure again.
Page 22
REMKO Smart WP MANAGER "Settings" menu item (continued) - User Authorisa- Level 2 Level 3 menu item Info tion level menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment...
Page 23
"Settings" menu item (continued) - User Authorisa- Level 2 Level 3 menu item Info tion level menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment 2nd mixed Time program A cycle Time program B Time program C...
Page 24
REMKO Smart WP MANAGER "Settings" menu item (continued) - User Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Number of power tariffs Heat pump Graduated tariff Time field Tariff 1-9 Power tariff 1-9...
Operation - Expert level 4.1 General notes regarding the menu structure of the controller The following information is primarily directed at specialist personnel. The following sections introduce the individual Enter the password “0321” by turning the menu items and parameters. You will find a brief rotary knob and by pressing of the "Next"...
Page 26
REMKO Smart WP MANAGER Overview of the menus (Expert level) Favourites LEVEL 0 3D house Hot water Room climate menu Main menu Chimney Manual Installation LEVEL 1 Information Settings Messages sweep mode wizard Basic Basic Start of the Error messages...
4.2 Commissioning wizard Assigning the unique unit identifier Here you can address up to 3 Smart Control units. When starting the controller for the first time the commissioning assistant is started in order to Select the unit identifier with the rotary knob and implement the basic programming of the existing confirm the entry with "OK".
Page 28
REMKO Smart WP MANAGER Setting the country Setting country-specific settings Select the country with the rotary knob and confirm Please confirm this parameter in order to load the the entry with "OK". country-specific settings. The selection of the country determines the setting for the date format, units of measurement and temperature limits.
Page 29
Factory Menu item Parameter setting Polski Setting the date Čeština Date 07 . 09 . 2017 Press "Next". Setting the time zone for the winter time Selecting the time zone for the winter time allows the switch to daylight savings time to occur auto- matically.
Page 30
REMKO Smart WP MANAGER Load user settings When first installing the controller this parameter is confirmed with "NO". Set the number of heat pumps in your If a new software status is installed after the initial installation. installation, it is possible to confirm this with "YES"...
Page 31
Operating mode Storage tank set temperature Desired charging temperature for the hot water storage tank. If there is a solar yield, the storage tank can become substantially warmer. The maximum tem- Choose between parallel and alternative perature for solar charging can be modified under operation mode.
Page 32
REMKO Smart WP MANAGER Hot water circulation Circulation type If there is a hot water circulation pump in the (dependent on which probes are used) building, which you are intending to operate in an Impulse circulation: energy-saving manner using the controller, this...
Page 33
Impulse-guided circulation - Impulse-guided circulation - Disable switch-on Running time of the circulation After the running time of the circulation pump, the Switch-on time of the circulation pump after a dis- pump cannot be started again while disable switch pensing impulse. on is active.
Page 34
REMKO Smart WP MANAGER Heating cycle mode Heating-curve heating cycle mode Unmixed cycle The heating curve can be adjusted in three points, according to the structure and location-related con- Optional: activate or deactivate the “Unmixed ditions of the building: cycle” function (select with the rotary knob and confirm with "OK").
Page 35
Setting the heating curve: Fixed-value-control heating cycle mode - Activate the base point with the right softkey, set Specify the set temperature for fixed value control with the rotary knob and conform with the right (select with the rotary knob and confirm with "OK"). softkey.
Page 36
REMKO Smart WP MANAGER Heating-curve heating cycle mode The heating curve can be adjusted in three points, Base point according to the structure and location-related con- ditions of the building: Base point: The base point corresponds to the minimum set temperature of the heating water at an outside temperature of 20 °C.
Page 37
Active cooling to operate inefficiently. The REMKO KWK wall and under ceiling units can be used to cool the rooms actively (inlet tempera- tures of below 10 °C) using the heat pumps.
Page 38
Active cooling The REMKO KWK wall and under ceiling units can After activating the 1st mixed cycle, the 2nd be used to cool the rooms actively (inlet tempera- mixed cycle is enabled.
Page 39
Separate cooling buffer Menu item Parameter Factory setting Separate Activated/ cooling deactivated Deactivated buffer Separate cooling bu er tank Press "Next". Separate cooling bu er tank deactivated Fig. 60: Activating the separate cooling buffer Setting the building time constant The building time constant specifies the ability of the building to retain heat. The building time constant is dependent upon the type of building (see table).
We recommend adapting plant-specific parameters, such a heating limits and bivalence point, to the design data! You can find further hydraulics examples at www.remko.de Hydraulic circuit diagram for heat pump SQW Package Cologne Configuration: Circuit unmixed, circuit 1 mixed, circuit 2 mixed, circuit 3 mixed, surface cooling, fresh water station.
Page 41
Basic settings for the SQW Package Cologne Menu item Parameter Factory setting Activate heat pump Activated/Deactivated Activated Auxiliary heat generator Activated/Deactivated Deactivated Domestic hot-water heating Activated/Deactivated Deactivated Storage tank set temperature "40°C - 65°C" 45 °C Hot water circulation Activated/Deactivated Deactivated Circulation type Impulse...
Page 42
REMKO Smart WP MANAGER Hydraulic circuit diagram for heat pump SQW Package Munich Cascade Configuration: Circuit unmixed, circuit 1 mixed, circuit 2 mixed, circuit 3 mixed, surface cooling, fresh water station. Operating mode: bivalent The operating mode in this case is bivalent but can also be monoenergetic! Only one cooling mode possible.
Page 43
Basic settings for the SQW Package Munich Cascade Menu item Parameter Factory setting Activate heat pump Activated/Deactivated Activated Auxiliary heat generator Activated/Deactivated Deactivated Domestic hot-water heating Activated/Deactivated Deactivated Storage tank set temperature "40°C - 65°C" 45 °C Hot water circulation Activated/Deactivated Deactivated Circulation type...
Page 44
REMKO Smart WP MANAGER Hydraulic circuit diagram for heat pump SQW Package Cologne RWS Configuration: Circuit unmixed, fresh water station. Operating mode: bivalent The operating mode in this case is bivalent but can also be monoenergetic! This hydraulic diagram serves merely to assist in planning activities;...
Page 45
Basic settings for the SQW Package Cologne RWS Menu item Parameter Factory setting Activate heat pump Activated/Deactivated Activated Auxiliary heat generator Activated/Deactivated Deactivated Domestic hot-water heating Activated/Deactivated Deactivated Storage tank set temperature "40°C - 65°C" 45 °C Hot water circulation Activated/Deactivated Deactivated Circulation type...
REMKO Smart WP MANAGER 4.4 Menu structure of the controller "Information" menu item - Expert This menu contains information about the current operating status of the system. The menu is opened with the key on the right. By turning the rotary knob, you can select another menu item (for instance "Settings").
Page 47
"Information" menu item (continued) - Expert Authorisa- Level 2 Level 4 menu Level 3 menu item Info tion level menu item item Hardware control panel Hardware Software control panel Version number Basic infor- mation (cont.) Software Linux kernel con- trol panel Linux kernel Licence information You can find...
Page 48
REMKO Smart WP MANAGER "Information" menu item (continued) - Expert Authorisa- Level 2 Level 3 menu item Info tion level menu item Operating mode Set temp. Actual temp. Inlet temp. S09 Return temp. S10 Room set temp. Room actual temp.
Page 49
"Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Heating energy 1st mixed Cooling energy cycle KNX status (cont.) KNX setpoint adjustment Operating mode Set temp. Actual temp. Inlet temp. S13 Return temp.
Page 50
REMKO Smart WP MANAGER "Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Set temp. Actual temp. Inlet temp. S15 Return temp. S16 Room set temp. Room actual temp.
Page 51
"Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 Level 4 menu item Info tion level item menu item Heat pump status Remaining idle time Compressor status Defrost status Fault status Enable signal Disable compressor Heat pump mode 1.
Page 52
REMKO Smart WP MANAGER "Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 Level 4 menu item Info tion level item menu item Heat pump Air temperature AM Water inlet temperature Water inlet temperature Suction gas temperature...
Page 53
"Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Heat generator status Potential-free output A32 Auxiliary heat Enable generator Enable time (minutes) Enable time (hours) Therm. power, heat pump Therm.
Page 54
REMKO Smart WP MANAGER "Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Current household output Household energy (day) Household energy (week) Household Household energy (month) Household energy (year)
Page 55
"Information" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item HW storage tank actual temp. S03 HW storage tank actual temp. S04 Circulation request S05 Circ. actual temp. S05 Outside temperature S06 Buffer tank temp.
Page 56
REMKO Smart WP MANAGER "Settings" menu item - Expert In this menu you can configure the settings. For example, you can adjust hot water and heating tempera- tures or change time settings. The menu is opened with the key on the right. Pressing the left-hand key allows you to jump up a level in the menu structure again.
Page 57
"Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Smart Com Interface search IP for the KNX interface IA for the KNX interface Multicast address IA for the controller Programming mode On/off (switching) Heating/cooling (switching)
Page 58
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Unmix. cycle humidity 1st mixed cycle humidity. 2nd mixed cycle humidity 3rd mixed cycle humidity...
Page 59
"Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Heat pump Auxiliary heat generator PV power utilisation Graduated tariffs Domestic hot-water heating Hot water circulation You can find Hygiene function many of the indi- vidual info texts...
Page 60
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Storage tank set temp. Mode Time program A Domestic hot water Time program B...
Page 61
Factory-set circulation switching times Designation Value range Factory setting Customer system Time program Mon-Sun Mon-Sun 00:00-24:00 Hygiene function Designation Value range Factory setting Customer system Set temperature "60 °C - 75 °C" 60 °C Day of activation Mon-Sun Monday Time of activation Hrs/Mins 20:00 Test time...
Page 62
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item Building time constant Standard outdoor temp. (heating) Standard outdoor temp. Building adaptation (cooling) Max. cooling down (outside temp.
Page 63
"Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B Time program C Time program function Room temperature decrease...
Page 64
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment...
Page 65
"Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B Time program C Time program function Room temperature decrease...
Page 66
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Info tion level item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment...
Page 67
Unmixed & mixed cycle switching times Designation Factory setting Customer system Time program A Mo-Su 00:00-24:00 Time program B Mo-Fr 05:00-23:00 Sa-Su 06:00-23:00 Time program C Mo-Fr 05:00-23:00 Sa-Su 06:00-23:00 "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info...
Page 68
REMKO Smart WP MANAGER "Settings" menu item (continued) - Expert Authorisa- Level 2 menu Level 3 menu item Level 4 menu item Info tion level item PV personal use variant Power tariff 1 Feed-in tariff Personal use tariff Damping electr. power...
Page 69
"Chimney sweep" menu item - Expert Authorisa- Level 2 menu item Level 3 menu item Info tion level Mode Normal operation/test mode Info texts can be Hot water valve Deactivated/activated found in the Smart Control Running time 15 - 90 minutes Mode test mode DHW valve deactivated...
Page 70
REMKO Smart WP MANAGER "Messages" menu item - Expert Pressing "OK" (right softkey) takes you to submenus of the menu item "Messages". This is where operating messages, warning notices and fault messages are displayed. Explanation of symbols: Warning message Fault message If one of these symbols appears in the header of the control screen, please access the menu item "Mes-...
Page 71
"Message" menu item (continued) - Expert Manual mode (relay test) (continued) Parameter Output Selection parameter open stop Open mixing valve for 1st mixed cycle close auto open stop Close mixing valve for 1st mixed cycle close auto open stop Open mixing valve for 2nd mixed cycle close auto...
Page 72
REMKO Smart WP MANAGER "Message" menu item (continued) - Expert Manual mode (relay test) (continued) Parameter Output Selection parameter auto Alarm signal closed open auto Pump unmixed cycle auto Speed auto Pump 1st mixed cycle auto Speed auto Pump 2nd mixed cycle...
Page 73
Manual mode (probes) Parameter Selection parameter Probes Manual mode Permanent Deactivated 15 minutes Probe value Storage tank temperature, lower Default value "-60°C - 250°C" Probe value Storage tank temperature, upper Default value "-60°C - 250°C" Circulation paddle switch Auto Probe value Outside temperature Default value "-60°C - 250°C"...
Page 74
REMKO Smart WP MANAGER "Message" menu item (continued) - Expert Manual mode (probes) (continued) Parameter Selection parameter Probe value Unmix. cycle medium flow rate Default value "Impulse 0 - 100 l/min” Probe value 1st mixed cycle medium flow rate Default value "Impulse 0 - 100 l/min”...
REMKO Smart WP MANAGER 5.2 Terminal block/legend Design. Input Output Signal Description Power supply I/O 230V Power supply for external consumer Reserve Reserve Bottom hot water tank probe Top hot water tank probe Circulation return flow temp./impulse Outside temperature probe...
Page 77
Design. Input Output Signal Description Reserve Reserve 230V changeover valve, cooling Mixing valve for 1st mixed cycle “open” Mixing valve for 1st mixed cycle “closed” Mixing valve for 2nd mixed cycle “open” Mixing valve for 2nd mixed cycle “closed” Mixing valve for 3rd mixed cycle “open” Mixing valve for 3rd mixed cycle “closed”...
REMKO Smart WP MANAGER 5.3 Sensors and probes Temperature probes If the sensor cables are too short, they can be The number of probes required can vary with extended up to a maximum of 100m with wire the type of system.
Fault messages on the Smart Control Operating messages, warnings and fault display on the Smart-Control Operating messages Description Desig. Details ID6008 Disable signal The heat pump is disabled due to a disable signal Random delay after power failure (up to 200 seconds after Random delay after power power returns) - the purpose of the random delay is to ID6108...
Page 90
REMKO Smart WP MANAGER Description Desig. Details Open contact - circulation Open contact - drinking water circulation temperature ID7210 temp. probe probe Short circuit - circulation ID7211 Short circuit - drinking water circulation temperature probe temp. probe Malfunction 1st heat pump - the specific fault message can ID7216 Heat pump malfunction be read on the heat pump’s display with address 1...
Page 91
Description Desig. Details The KNXnet/IP tunnelling protocol is not supported by the ID7248 Interface is not supported detected KNX interface The physical address of the detected KNXnet/IP interface Incorrect interface ID7249 is not consistent with the parameter settings of the SMT detected controller Due to the changed system (setting/coding resistor), the...
Page 92
REMKO Smart WP MANAGER Warnings Description Desig. Details The active operating mode is safety mode because the ID8107 Compressor status compressor is active without demand Anti-freeze protection The anti-freeze protection function is currently active - ID8132 active check the room climate mode set...
The Smart Control remote can be mounted to a wall, e.g. in the living room. For installation and commissioning of the REMKO Smart-Control remote control, follow To wall mount the Smart Control remote, proceed the corresponding instructions as follows: Fasten the wall bracket directly to the wall using screws and rawl plugs.
Page 96
SFlb Customer Service Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and REMKO GmbH & Co. KG reliable service.