3. Set the standard outside temperature
The standard outside temperature can be changed
in the user and expert level.
Here, it is possible to set the standard outside tem-
perature to the respective value for heating and
cooling mode.
The standard outside temperature is only changed
once here for each active heating circuit. After
changing this parameter, the value is automatically
accepted with all active heating circuits.
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Access this parameter as follows:
User level
Settings
Heating/cooling
Building adaptation
Standard outside temperature
Expert level
¯
¯
¯
¯
Fixed-value-control heating circuit mode
Specify the set temperature for fixed value control.
The heating circuit is kept permanently at this tem-
perature in fixed value control. When doing so, a
tolerance of approx. 2 Kelvin is possible.
User level
Settings
e.g. unmixed cycle
Fixed value
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat
pump to operate inefficiently.
The mixed heating cycles each require a supply
and return probe! These probes are included in the
scope of supply of the mixed REMKO heating cir-
cuit groups.
Activation of the cooling function via the
unmixed circuit
This is where you can select between the different
cooling circuit modes. The choice is between
control according to the set "cooling curve" and
"fixed value regulation".
Activation of the cooling function can take place in
every heating circuit via the operating mode.
Menu item
Parameter
Cooling circuit
Cooling curve
mode with
underfloor
Fixed value
system active
Expert level
¯
¯
¯
Factory set-
ting
According to
design
8 °C - 35 °C
27