Select standard analogue:
Mobile network:
Relay outputs A8 and A12:
O.C.-outputs A4, A8 and A12:
Programming connection:
Power supply:
Local alarm:
Max. current external buzzer :
Max. current external flashing light : 150mA
Capacity taken up:
Emergency power supply :
Emergency power supply reserve:
Logging:
Timer:
Mains cable length:
Telephone cable length:
Dimensions:
Degree of protection:
Weight:
Operating temperature :
NB: The specifications of the Octalarm-IP are indicative and subject to change.
User manual Octalarm-IP | version 11-2021
Tone code (only PSTN model)
2G or 3G quad band (depending on the GSM
module used). Automatic GSM quad band
switching is from firmware version RV-2.6.12
2 relay outputs (max. 24VDC / 1A)
2 open collector outputs (max.200mA)
UTP-connection for connecting to a computer or
internet modem
90-245VAC, 50-60Hz
Built-in alarm speaker
150mA
Type dependent max. 10W
NiMH battery with battery monitoring and trickle
charger
Type dependent. Battery capacity 2000mAh.
Built-in data logger with date and time
Adjustable clock with date and time Backup by
means of button cell battery
approx.1,5m
approx. 2m
233 x174 x55 mm (W x H x D)
IP33 (not splash proof)
Type dependent approx. 1,100 gram
-5° ... +50°
Adesys B.V. | Wateringen
Back to contents | Page 57