6. I/0 CONFIGURATION

6.1

INPUT CONFIGURATION (ONLY FOR OPTION 1 AND OPTION 2 MODELS)

The MIF incorporates 2 digital inputs, which can be configured using the ENERVISTA MII SETUP software. The
default input configuration is as follows:
Input 1: 50PH disabled &. 50PL disabled
Input 2: 50NH disabled & 50NL disabled.
All functions not defined as PULSE are LEVEL inputs.
The minimum operation time for a valid PULSE input is over 0.015 seconds.
Inputs functions are divided in 2 groups with up to eight functions per group, besides the No definition function. Up to
eight functions can be configured for the same input, provided that they are all in the same group. Functions
belonging to different groups need to be assigned to different inputs.
In order to configure an input with more than one function from the same group, first we must activate the OR button,
click on the I/O CONFIGURATION option and select the desired group, then select the desired functions. For
negating a function, select the NOT button. Finally, click the OK button.
For example, if we want only the thermal function to trip, we can disable the rest of functions, or we can assign the
rest of the disabled functions to one digital input, using an OR.
Input 1/2
If we want to reset LEDs using a digital input, we must assign the LED reset function to one digital input
Input 1/2
GEK-106273L
PRODUCT DESCRIPTION
MIF Digital Feeder Protection
6.1.1.

DESCRIPTION OF INPUTS

50PH disabled.
50NH disabled
51P disabled
51N disabled
50PL disabled
50NL disabled
Reset
6-39