GE GEK-106273L Instruction Manual page 178

Digital feeder protection
Table of Contents

Advertisement

CONFIRMATION:
Request:
FIELD
LENGTH
Relay address
1 Byte
Function
1 Byte (10H)
Beginning
1 word (0000H) (High byte – low byte)
No. of records
1 word (0003H) (High byte – low byte)
No. of bytes
1 Byte (06H)
Value of records
Record1=>Command code (High byte – low byte).
Record2=>Relay password (High byte – low byte).
Record3=>Constant value 0000H
CRC
1 word
Reply:
FIELD
LENGTH
Relay address
1 Byte
Function
1 Byte (10H)
Beginning address
1 word (0000H) (High byte – low byte)
No. of records
1 word (0003H) (High byte – low byte)
CRC
1 word
Example:
To confirm the activation of table 2, the operation code used will be 16 (10H). In this case, it is necessary to send the
relay password.
Request:
ADDRESS
FUNCTION
01
10
Reply:
ADDRESS
FUNCTION
01
10
GEK-106273L
ANNEX 3 MODBUS MEMORY MAP
BEGINNING
#REGS
00 00
00 03
BEGINNING
#REGS
00 00
00 03
MIF Digital Feeder Protection
#BYTES
DATA0
06
10 00
CRC
8008
DATA1
DATA2
CRC
01 00
00 00
E5EC
13-3

Advertisement

Table of Contents
loading