13.4
WRITING SETTINGS
There are three steps to write a settings:
1.
Executing a selection command using code 01 00H. (See command execution).
2.
Changing the setting
3.
Executing a confirmation command using code (See command execution).
For modifying a setting, we will use function 10H (PRESET MULTIPLE REGISTERS de MODBUS
FIELD
LENGTH
Relay address
1 Byte
Function
1 Byte (10H)
Beginning
1 word (High byte – low byte)
No. of records
1 word (High byte – low byte)
No. of bytes
1 Byte
Value of the records
(High byte – low byte)
CRC
1 word
Reply:
FIELD
LENGTH
Relay address
1 Byte
Function
1 Byte (10H)
Beginning address
1 word
No. of records
1 word
CRC
1 word
Example:
In this example, we will modify the Identification setting of a relay that stores this information in position
0118H of its memory map. The relay identification is an ASCII text of 16 characters.
1. SETTING CHANGE SELECTION (LIKE A COMMAND)
Request:
ADDRESS
FUNCTION
01
10
Reply:
ADDRESS
FUNCTION
01
10
GEK-106273L
ANNEX 3 MODBUS MEMORY MAP
BEGINNING
#REGS
0000
0001
BEGINNING
#REGS
0000
00 01
MIF Digital Feeder Protection
#BYTES
DATA0
CRC
02
0100
A7C0
CRC
01C9
®
)
13-5