GE GEK-106273L Instruction Manual page 140

Digital feeder protection
Table of Contents

Advertisement

RELAY COMMISSIONING
9.21
USER SETTINGS
The following pages intend to be useful to register the user settings. They can be used as a guide or
template, to record the relay settings, in case your company does not provide a proprietary form sheet.
GENERAL SETTINGS
Relay Status
Frequency
Phase CT ratio
Neutral CT ratio
Password
Address
Communications Speed
Phase TOC Function
51P Permission to Trip
51P Tap / Pickup Value
51P Curve Type
51P Time Dial
51P Definite Time Delay
Ground TOC Function
51N Permission to Trip
51N Tap / Pickup (1/5 A
ground)
51N Tap / Pickup
(sensitive ground)
51N Curve Type
51N Time Dial
51N Definite Time Delay
Phase
IOC
High
Setting
50PH Permission to Trip 50PH Trip Permission
50PH Tap / Pickup
50PH Time Delay
GEK-106273L
ENERVISTA MII
SETUP
GENERAL
GENERAL
SETTINGS
RELAY STATUS
FREQUENCY
PHASE TRANSF
RATIO
NEUTRAL TRANSF
RATIO
---
---
---
51P Function
51P Trip Permission
51P Pickup
51P Curve Type
CURV 51P
51P Time Dial
51P Definite Time
TIME 51P
51N Function
51N Trip Permission
TRIP 51N
51N Pickup
51N Pickup
51N Curve Type
CURV 51N
51N Time Dial
51N Definite Time
TIME 51N
50PH Function
50PH Pickup
TAP 50PH
50PH Time Delay
MIF Digital Feeder Protection
USER
HMI
VALUE
STA
FRQ
CT PH
CT PH
PWD
ADD
BAUD
F51P
TRIP 51P
TAP 51P
DIAL 51P
F51N
TAP 51N
TAP 51N
DIAL 51N
F50PH
TRIP
TIME
9.21.1.
MAIN SETTINGS
RANGE
RDY / DIS
50/60 Hz
1-4000
1-4000
1 – 255
1 – 255
300, 600, 1200, 2400,
4800, 9600, 19200
Y/N
0.1-2.4 In (Ph)
INV, V.I., E.I., T.DE
0.05 – 2.00 (IEC)
0.5 – 20.0 (ANSI)
0 – 600.00 s.
Y/N
0.1 – 2.4 In (Gnd)
0.005-0.120 A
INV, V.I., E.I., T.DE
0.05 – 2.00 (IEC)
0.5 – 20.0 (ANSI)
0 – 600.00 s.
Y/N
0.1 – 30 In (Ph)
0 – 600.00 s.
STEP
NA
NA
1
1
1
NA
NA
0.01 In
NA
0.01
0.01
0.01 s.
NA
0.01 In
(Gnd)
0.001 A
NA
0.01
0.01
0.01 s.
NA
0.1 In (Ph)
0.01 s.
9-13