Set 1
DESCRIPTIÓN
1
112 ETD/OFF
ON: Circuit 112 connected to ETD
OFF: Circuit 112 connected to ETD
2
112 ETD/ON
ON: 108 circuit forced to CLOSED.
OFF: 108 circuit follows ETD's 108 circuit
3
105 ETD/ON
ON: Circuit 105 forced to CLOSED.
OFF: Circuit 105 follows ETD's 105circuit
4
TXA/TXB in a peer-to-peer line (PP)
ON: In PP transfers through high channel.
OFF: In PP transfers through low channel.
5&6
Baud rate selection for data transfer.
ON-ON
1200
OFF-ON
2400
ON-OFF
Automatic.
OFF-OFF
Automatic.
7&8
Automatic disconnection.
ON-ON
No automatic disconnection.
OFF-ON
Circuit 105.
ON-OFF
Circuit 109.
OFF-OFF
Circuits 105 and 109.
Set 2
DESCRIPTIÓN
1
Synchronous format of protocol V25bis in option 108.2.
ON: Character oriented format (BSC).
OFF: Bit oriented format (HDLC).
2&3
Asynchronous character format for data transfer
ON-ON
8
OFF-ON
9
ON-OFF
10
OFF-OFF
11
4
Reception permission for remote loop 2
ON: Not permitted.
OFF: Permitted.
5&6
Exploitation mode.
ON-ON
Point-to-point line
OFF-ON
Automatic call as per 108.1.
ON-OFF
RTC line without automatic call.
OFF-OFF
Automatic call as per 108.2.
7
Number of calls for automatic answer
ON: 1 call.
OFF: 2 calls.
8
112 ETD/OFF
ON: Asynchronous operation.
OFF: Synchronous operation.
GEK-106273L
ANNEX 4 MODEM CONNECTION
LOCATION OF MODEM MICROSWITCHES ON THE RELAY SIDE
MIF Digital Feeder Protection
VALUE
ON
ON
ON
ON
ON-OFF
OFF-OFF
VALUE
ON
ON-OFF
OFF
ON-OFF
OFF
ON
14-7