Configuration of output at terminals B8-B7:
To have a close contact across terminal B7-B8, one of the two following procedures should be followed:
•
Jx Removed and OUT1 and OUT2 normally open:
OUT1 and OUT2 must operate together to operate like a single output. The configuration of OUT1 and OUT2 must
be the same so both outputs close simultaneously and operate successfully.
•
Jx Removed and one of the two internal contacts set as normally closed:
3-34
PRODUCT DESCRIPTION
MIF Digital Feeder Protection
GEK-106273L