Phase / Ground Toc Settings (51P / 51N) - GE GEK-106273L Instruction Manual

Digital feeder protection
Table of Contents

Advertisement

Phase TOC Function
51P
Permission
to
Trip
51P Tap / Pickup
Value
51P Curve Type
51P Time Dial
51P
Definite
Time
Delay
Ground
TOC
Function
51N
Permission
to
Trip
51N Tap / Pickup (for
1/5 A ground)
51N Tap / Pickup (for
sensitive ground)
51N Curve Type
51N Time Dial
51N
Definite
Time
Delay
GEK-106273L
PRODUCT DESCRIPTION
ENERVISTA MII
SETUP
51P Function
51P Trip Permission
51P Pickup
51P Curve Type
51P Time Dial
51P Definite Time
51N Function
51N Trip Permission
51N Pickup
51N Pickup
51N Curve Type
51N Time Dial
51N Definite Time
MIF Digital Feeder Protection
5.2.2.

PHASE / GROUND TOC SETTINGS (51P / 51N)

HMI
DEFAULT
F51P
TRIP 51P
No
TAP 51P
0.5 In (Phase)
CURV 51P
T.DE
DIAL 51P
0.5
5
TIME 51P
1 s.
F51N
TRIP 51N
No
0.5 In
TAP 51N
(Ground)
TAP 51N
0.005 A
CURV 51N
T.DE
DIAL 51N
0.5
5
TIME 51N
1 s.
RANGE
STEP
Y/N
NA
0.1-2.4 In (Ph)
0.01 In (Ph)
INV, V.I., E.I.,
NA
T.DE
0.05 – 2.00
0.01
(IEC curves)
0.5 – 20.0
0.01
(ANSI curves)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 2.4 In
0.01 In
(Gnd)
(Gnd)
0.005-0.12 A
0.001 A
INV, V.I., E.I.,
NA
T.DE
0.05 – 2.00
0.01
(IEC curves)
0.5 – 20.0
0.01
(ANSI curves)
0 – 600.00 s.
0.01 s.
5-29